特高壓交流變電站GIS母線故障綜合分析法
吳展鋒,孫彥萍,徐慶峰,彭晨光,常騰飛
(國(guó)網(wǎng)浙江省電力有限公司檢修分公司,浙江 杭州 311232)
摘 要:GIS母線故障在大部分情況下是外觀無(wú)異常,無(wú)異常氣味,無(wú)氣體泄漏的聲音,看不到明顯的故障點(diǎn)。針對(duì)無(wú)明顯故障點(diǎn)的GIS母線故障,提出了一種GIS母線故障綜合分析法,通過(guò)氣室壓力分析法、零序電流分析法、紅外測(cè)溫分析法及六氟化硫(SF6)氣體組分分析法來(lái)綜合判斷故障部位。此方法在快速大致定位故障氣室的前提下,有針對(duì)性地進(jìn)行組分分析,可快速、可靠定位故障點(diǎn),從而進(jìn)行故障氣室的隔離,恢復(fù)母線的運(yùn)行,實(shí)際案例分析驗(yàn)證了該方法的有效性。
關(guān)鍵詞:特高壓;GIS 母線;綜合分析;故障定位
中圖分類號(hào):TM595 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2020)07-0039-05
A Comprehensive Analysis Method of GIS Bus Fault in UHV AC Substation
WU Zhan-feng, SUN Yan-ping, XU Qing-feng, PENG Chen-guang, CHANG Teng-fei
(Maintenance Company of State Grid Zhejiang Electric Power Company, Hangzhou 311 232, China)
Abstract: In most cases, there is no abnormal appearance, no abnormal smell, no sound of gas leakage, and no obvious failure point can be seen in GIS bus fault.Aiming at GIS bus faults without obvious fault points, a comprehensive analysis method for GIS bus faults is proposed. The fault is comprehensively judged by gas chamber pressure analysis method, zero sequence current analysis method, infrared temperature measurement analysis method and SF6 gas component analysis method Location.This method is based on the premise of quickly and roughly locating the faulty gas chamber, and conducts targeted component analysis to quickly and reliably locate the fault point, thereby isolating the faulty gas chamber and restoring the operation of the bus.The actual case analysis verifies the effectiveness of the method.
Key words: UHV; GIS bus; comprehensive analysis; fault location
參考文獻(xiàn)
[1] 劉振亞. 中國(guó)特高壓交流輸電技術(shù)創(chuàng)新[J]. 電網(wǎng)技術(shù),2013,37(3):T1-T8.
[2] 樊東峰,張建立. 特高壓輸變電工程環(huán)保糾紛產(chǎn)生原因及對(duì)策探討[J]. 華中電力,2011,24(4):41-44.
[3] 康莉娟, 王雨新. 淺談S F6 氣體絕緣全封閉組合電器(GIS)的運(yùn)行維護(hù)管理[J]. 科技信息,2011(26):328-330.
[4] 王思華. 全封閉組合電器結(jié)構(gòu)分析及其存在的問(wèn)題[J]. 電氣開(kāi)關(guān),2009,47(3):3-5.
[5] 鄭燁,謝玖榮,黃海,等. 封閉式組合電器典型故障分析及預(yù)防措施[J]. 電工電氣,2015(8):59-60.
[6] 池威威,劉倩,董俊虎,等.1 000 kV特高壓GIS絕緣故障及實(shí)例分析[J]. 河北電力技術(shù),2018,37(1):10-12.
[7] 李乃永,張輝,蘇欣,等. 氣體絕緣全封閉組合電器母線跳閘快速恢復(fù)方案[J]. 電力系統(tǒng)自動(dòng)化,2015,39(22):170-175.
[8] 安濱.1 000 kV GIS設(shè)備故障檢測(cè)及實(shí)例分析[J].電工電氣,2019(8):46-49.
[9] 王一,黃超,顧水平,等. 一種GIS故障快速定位方法[J]. 浙江電力,2017,36(2):43-46.
[10] 胡全義,秘立鵬,劉天奇,等. 一起GIS設(shè)備漏氣及現(xiàn)場(chǎng)交流耐壓試驗(yàn)擊穿故障分析[J]. 電工電氣,2017(8):43-46.
[11] 劉永,印華,姚強(qiáng),等. 氣體分析技術(shù)在GIS故障定位和故障類型判斷中的應(yīng)用[J]. 高壓電器,2009,45(3):132-134