環(huán)氧樹(shù)脂絕緣站用變壓器局部異常發(fā)熱檢測(cè)分析與消除

來(lái)源:電工電氣發(fā)布時(shí)間:2021-11-19 08:19 瀏覽次數(shù):550

環(huán)氧樹(shù)脂絕緣站用變壓器局部異常發(fā)熱檢測(cè)分析與消除

劉泊辰1, 郝洪民1, 苗軍1, 咸日常2, 陳蕾2, 郭洋2, 李佳琪2
(1 國(guó)網(wǎng)山東省電力公司淄博供電公司,山東 淄博 255000;
2 山東理工大學(xué) 電氣與電子工程學(xué)院,山東 淄博 255000)
 
    摘 要:由于站用變壓器長(zhǎng)期運(yùn)行在高電壓、高場(chǎng)強(qiáng)和負(fù)載電流條件下,所處環(huán)境工況復(fù)雜,其絕緣性能失效事件時(shí)有發(fā)生。通過(guò)紅外熱像儀測(cè)溫、長(zhǎng)焦相機(jī)拍照的帶電檢測(cè)方法,結(jié)合離線電氣試驗(yàn),分析了一起 35 kV 干式絕緣站用變壓器因局部機(jī)械受損、運(yùn)行環(huán)境濕度大,從而導(dǎo)致其繞組環(huán)氧樹(shù)脂絕緣性能下降并發(fā)生沿面放電,進(jìn)而引起局部異常發(fā)熱的案例,并介紹了修復(fù)方案和預(yù)防措施,為保障站用變壓器的安全穩(wěn)定運(yùn)行和維修試驗(yàn)提供了參考。
    關(guān)鍵詞:站用變壓器;帶電檢測(cè);絕緣性能;沿面放電;異常發(fā)熱
    中圖分類號(hào):TM401     文獻(xiàn)標(biāo)識(shí)碼:B    文章編號(hào):1007-3175(2021)11-0047-04
 
Detection Analysis and Elimination of Local Abnormal Heating of Epoxy
Resin Insulated Station Transformer
 
LIU Bo-chen1, HAO Hong-min1, MIAO Jun1, XIAN Ri-chang2, CHEN Lei2, GUO Yang2, LI Jia-qi2
(1 State Grid Shandong Electric Power Company Zibo Power Supply Company, Zibo 255000, China;
2 School of Electrical and Electronic Engineering, Shandong University of Technology, Zibo 255000, China)
 
    Abstract: The insulation failure event of station transformers is a frequent occurrence due to the long-term operation of the transformers for power stations under high voltage and high electric stress, overload current, and complex working conditions. This paper analyzed a typical case a 35 kV dry-type insulation substation transformer has a local heating phenomenon. The phenomenon is caused by the insulation of epoxy resin winding decreasing and creeping discharge, which was triggered by the mechanical fault and high environmental relative humidity.This article introduces the repair plan and preventive measures, which could provide a reference for ensuring the safe and stable operation and maintenance test of the transformers for power stations.
    Key words: station transformer; live detection; insulation performance; creeping discharge; abnormal heating
 
參考文獻(xiàn)
[1] 張鵬,齊波,李成榕,等.電力變壓器油中溶解氣體特性影響因素的量化分析[J].中國(guó)電機(jī)工程學(xué)報(bào),2021,41(10) :3620-3631.
[2] 陳蕾,咸日常,鄭春旭,等.系統(tǒng)單相接地故障下接地變壓器的運(yùn)行特性分析[J].電力系統(tǒng)保護(hù)與控制,2021,49(12) :56-64.
[3] 秦川,李景燦,范鎮(zhèn)南.35 kV 站用變壓器爆炸事故分析[J].變壓器,2021,58(2) :85-87.
[4] 付軼,劉濤,梁仕斌,等.35 kV 站用變壓器直流電阻異常分析[J].云南電力技術(shù),2019,47(2) :39-42.
[5] 端木林楠,趙習(xí)靜,蔡巍,等.某 220 kV 變電站 35 kV 站用變壓器爆炸事故分析與處理[J].高壓電器,2015,51(12) :174-178.
[6] 謝耀恒,雷紅才,黃海波,等.環(huán)氧樹(shù)脂濕熱老化過(guò)程分子模擬仿真研究[J].絕緣材料,2019,52(9) :70-77.
[7] 楊敏,王新,童小忠,等.環(huán)氧樹(shù)脂/Al2O3 納米復(fù)合材料直流電樹(shù)枝及局部放電特性研究[J].絕緣材料,2021,54(6) :49-55.
[8] 池明赫,李毅恒,羅青林,等.運(yùn)行環(huán)境對(duì)換流變壓器油紙絕緣電場(chǎng)分布的影響[J].電機(jī)與控制學(xué)報(bào),2021,25(5) :71-79.
[9] 王永強(qiáng),仲釗,謝軍,等.溫度對(duì)不同老化程度的絕緣紙板沿面放電的影響[J].高電壓技術(shù),2017,43(8) :2724-2732.