應用于高海拔環(huán)境下的550 kV GIS套管抗震性能分析

來源:電工電氣發(fā)布時間:2021-11-19 09:19 瀏覽次數(shù):496

應用于高海拔環(huán)境下的550 kV GIS套管抗震性能分析

劉偉, 劉傳會,劉秀君
(山東彼岸電力科技有限公司,山東 濟南 250200)
 
    摘 要:對設計并應用于云南某高海拔地區(qū)的 550 kV GIS 套管進行抗震性能分析,參照設計圖紙構建三維模型,利用模態(tài)分析確定套管設計結構的固有頻率和振型,對套管施加內部壓力、風載荷及靜態(tài)端子負荷,采用響應譜分析計算出套管在 AG5 水平下各零部件的位移與應力。計算結果表明,所設計的 550 kV GIS 套管安全系數(shù)滿足 AG5 水平要求,可以安全使用,但套管頂部均壓環(huán)位移相對較大,應充分考慮預留頂端導線接線長度。
    關鍵詞:高海拔;GIS 套管;抗震性能分析;模態(tài);響應譜
    中圖分類號:TM643     文獻標識碼:A     文章編號:1007-3175(2021)11-0039-04
 
Seismic Performance Analysis of 550 kV GIS Casing at High Altitude
 
LIU Wei, LIU Chuan-hui, LIU Xiu-jun
(Shandong Peiport Electric Power Technology Co., Ltd, Jinan 250200, China)
 
    Abstract: This article evaluated the structural seismic performance of 550 kV GIS casing, which was designed and applied in a high altitude area in Yunnan province. This research constructed a three-dimensional model. It determined the natural frequency and vibration mode of the casing design structure by analyzing this model. The internal pressure, wind load, and static terminal load have been applied to the casing.This paper calculated the displacement and stress of each part of the casing under the AG5 level by using the response spectrum analysis.The calculation results show that the safety factor of 550 kV GIS casing meets the requirements of the AG5 level. However, the displacement of the grading ring at the top of the casing is relatively large, so it is necessary to consider the wire connection length at the top.
    Key words: high altitude; GIS casing; seismic performance analysis; model; response spectrum
 
參考文獻
[1] 聶德鑫,鄧鶴鳴. 高壓套管技術標準發(fā)展現(xiàn)狀[J].電瓷避雷器,2021(2) :7-13.
[2] 余榮興,曹枚根,張若愚,等. 特高壓復合直流避雷器地震響應及結構參數(shù)影響分析[J] . 電瓷避雷器,2021(1) :131-137.
[3] 曹永興,鄧鶴鳴,蔡煒,等. 電力設施應對地震及其次生災害的研究進展[J] . 高電壓技術,2019,45(6) :1962-1974.
[4] 孫幫新,曹枚根. 特高壓新松換流站直流場設備抗震設計及能力考核[J]. 高壓電器,2018,54(12) :24-35.
[5] 肖淦, 昌明輝, 吳學恩, 等. 淺析高海拔地區(qū)使用的套管內絕緣長度改變[J] . 變壓器,2017,54(10) :10-13.
[6] 中華人民共和國國家質量監(jiān)督檢驗檢疫總局. 高壓開關設備和控制設備的抗震要求:GB/T 13540—2009[S]. 北京:中國標準出版社,2010 :5-9.
[7] 黎斌.SF6 高壓電器設計[M]. 北京:機械工業(yè)出版社,2019.
[8] 孫宇晗,程永鋒,盧智成,等. 特高壓 GIS 瓷質套管與復合套管抗震性能試驗研究[J] . 高電壓技術,2019,45(2) :541-548.