Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁(yè) >> 文章檢索 >> 往年索引

基于局放定位的變壓器鐵芯多點(diǎn)接地故障診斷分析

來源:電工電氣發(fā)布時(shí)間:2022-01-20 11:20 瀏覽次數(shù):584

基于局放定位的變壓器鐵芯多點(diǎn)接地故障診斷分析

邱煒,高竣,劉鑫,劉彥琴,楊紅權(quán),周波,郭超,程鵬,林岑
(國(guó)網(wǎng)四川省電力公司成都供電公司, 四川 成都 610041)
 
    摘 要:針對(duì)某 110 kV 主變?cè)谶\(yùn)行中發(fā)現(xiàn)絕緣油中乙炔及總烴含量超標(biāo)的問題,通過特高頻、超聲波等帶電檢測(cè)手段對(duì)主變內(nèi)部缺陷進(jìn)行分析和定位,并采用基于特高頻局放信號(hào)的平分面法精確找到了放電缺陷的位置,通過對(duì)主變吊罩發(fā)現(xiàn)鐵芯存在間歇性多點(diǎn)接地,成功驗(yàn)證了局放定位的準(zhǔn)確性,經(jīng)過分析放電原因及過程,給出了處理此類問題的應(yīng)對(duì)建議。
    關(guān)鍵詞:主變;局放定位;鐵芯;多點(diǎn)接地;油色譜
    中圖分類號(hào):TM407     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2022)01-0036-06
 
Multi-Point Grounding Fault Diagnosis of the Transformer Iron Core
Based on PD Positioning Method
 
QIU Wei, GAO Jun, LIU Xin, LIU Yan-qin, YANG Hong-quan, ZHOU Bo, GUO Chao, CHENG Peng, LIN Cen
(Chengdu Power Supply Company, State Grid Sichuan Electric Power Company, Chengdu 610041, China)
 
    Abstract: The acetylene and total hydrocarbon in the insulating oil exceed the criteria is a problem that exists in the operation of the 110 kV main transformer. This research used hot-line detection methods, such as ultra-high frequency (UHF) and ultrasonic waves, to analyze and locate the defects of the main transformer. It employed the bisection plane based on ultra-high frequency partial discharge signal to find the location of the discharge defect as well.The article also found the intermittent multi-point grounding of the iron core through the main transformer hanging cover and successfully verified the accuracy of the partial discharge positioning. It proposes suggestions to manage these problems after analyzing the cause and process of the discharge.
    Key words: main transformer; PD positioning; iron core; multi-point grounding; oil chromatography
 
參考文獻(xiàn)
[1] 周電波,王紅梅,程江榮,等. 變壓器局部放電多頻段聯(lián)合檢測(cè)技術(shù)試驗(yàn)研究[J] . 高壓電器,2018,54(11) :170-175.
[2] 郭志楠,韓洪剛,郭鐵,等. 一臺(tái) 220 kV 變壓器油色譜異常分析與處理[J] . 變壓器,2020,57(8) :64-66.
[3] STONE G C.Partial discharge diagnostics and electricalequipment insulation condition assessment [J] . IEEE Transactions on Dielectrics and Electrical Insulation,2005,12(5) :891-904.
[4] 李德軍,沈威,郭志強(qiáng). GIS 局部放電常規(guī)檢測(cè)和超聲波檢測(cè)方法的應(yīng)用比較[J] . 高壓電器,2009,45(3) :99-103.
[5] 劉宏亮,丁斌,高樹國(guó),等. 基于寬頻帶脈沖電流法的變壓器局部放電多端檢測(cè)技術(shù)研究[J] . 高壓電器,2018,54(11) :233-238.
[6] 汪一雄,方毅平,董卓,等. 變壓器鐵芯夾件多點(diǎn)接地故障分析處理[J] . 湖南電力,2016,36(3) :69-72.
[7] 王克峰,孫慶生,江和順,等. 一起 500 kV 變壓器穩(wěn)釘懸浮放電故障的診斷與分析[J] . 高壓電器,2012,48(3) :95-98.
[8] 楊春,孟麗坤,徐佩,等. 一起 500 kV 變壓器局部過熱故障分析[J]. 變壓器,2021,58(2) :82-84.
[9] 羅旖旎,黃超. 變壓器繞組的局部放電定位研究[J]. 變壓器,2009,46(3) :43-46.
[10] 劉彥琴,劉君,周波,等. 聲電聯(lián)合法在主變局放缺陷定位中的現(xiàn)場(chǎng)應(yīng)用[J] . 高壓電器,2018,54(11) :239-244.
[11] 葛為民. 變壓器局部放電超聲定位的現(xiàn)場(chǎng)應(yīng)用[J].高壓電器,2005,41(5) :351-353.
[12] 王國(guó)利,郝艷捧,李彥明. 電力變壓器局部放電定位方法的現(xiàn)狀和前景[J]. 變壓器,2001,38(11) :22-27.