預(yù)裝式變電站接地回路短時(shí)耐受電流及導(dǎo)體截面積探討

來(lái)源:電工電氣發(fā)布時(shí)間:2022-03-24 10:24 瀏覽次數(shù):593

預(yù)裝式變電站接地回路短時(shí)耐受電流及導(dǎo)體截面積探討

王鵬程
(正泰電氣股份有限公司,上海 201614)
 
    摘 要:應(yīng)用于10 kV 電壓等級(jí)的配電網(wǎng)中的預(yù)裝式變電站,接地回路的額定短時(shí)耐受電流的參數(shù)值和導(dǎo)體截面積的選擇直接關(guān)系到產(chǎn)品的安全、可靠運(yùn)行。從預(yù)裝式變電站中變壓器的高壓側(cè)和低壓側(cè)預(yù)期的短路電流出發(fā),確定出變壓器低壓側(cè)短時(shí)耐受電流值和接地回路導(dǎo)體截面積,以此為基點(diǎn),結(jié)合高壓側(cè)接地回路的額定短時(shí)耐受電流和導(dǎo)體截面積,最終確定出預(yù)裝式變電站的接地回路的額定短時(shí)耐受電流、短路持續(xù)時(shí)間及導(dǎo)體截面積,作為預(yù)裝式變電站產(chǎn)品設(shè)計(jì)和型式試驗(yàn)的選用依據(jù)。
    關(guān)鍵詞:變壓器;電弧故障電流;接地回路導(dǎo)體截面積;額定短時(shí)耐受電流Ike ;短路持續(xù)時(shí)間tke
    中圖分類(lèi)號(hào):TM63     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2022)03-0059-04
 
Discussion on Short-Time Withstand Current and Conductor Section of
Grounding Circuit in Prefabricated Substation
 
WANG Peng-cheng
(Chint Electric Co., Ltd, Shanghai 201614, China)
 
    Abstract: The prefabricated substation is used in a distribution network of 10 kV voltage level. The parameter value of the rated shorttime withstand current of the ground loop and the selection of the conductor cross-sectional area are directly related to its safe and reliable operation.This paper studied the short-circuit current of the high-voltage side and low-voltage side of the prefabricated transformer to determine the short-time withstand current value of the low-voltage side of the transformer and the cross-sectional area of the grounding circuit conductor.This research combined the rated short-time withstand current and conductor cross-sectional area of the high-voltage side ground loop based on the short-time withstand current value of the low-voltage side of the transformer and the cross-sectional area. It determined the rated short-time withstand current, short-circuit duration, and conductor cross-sectional area of the grounding loop. It indicates that these factors could be the basis of the selection of the product design and type test of the prefabricated substation.
    Key words: transformer; arc fault current; cross-sectional area of grounding circuit conductor; rated short-time withstand current Ike; shortcircuit duration tke
 
參考文獻(xiàn)
[1] 中國(guó)電器工業(yè)協(xié)會(huì). 高壓/低壓預(yù)裝式變電站:GB/T17467—2020[S] . 北京:中國(guó)標(biāo)準(zhǔn)出版社,2020 :6-12.
[2] 中國(guó)電器工業(yè)協(xié)會(huì). 低壓成套開(kāi)關(guān)設(shè)備和控制設(shè)備第 1 部分:總則:GB 7251.1—2013[S]. 北京:中國(guó)標(biāo)準(zhǔn)出版社,2013 :57-64.
[3] 中國(guó)電器工業(yè)協(xié)會(huì).3.6 kV~40.5 kV 交流金屬封閉開(kāi)關(guān)設(shè)備和控制設(shè)備:GB/T 3906—2020[S]. 北京:中國(guó)標(biāo)準(zhǔn)出版社,2020 :75.
[4] 全國(guó)電壓電流等級(jí)和頻率標(biāo)準(zhǔn)化技術(shù)委員會(huì). 標(biāo)準(zhǔn)電流等級(jí): GB/T 762—2002[S]. 北京:中國(guó)標(biāo)準(zhǔn)出版社,2002 :1.