新投運1 000 kV特高壓并聯(lián)電抗器產生乙炔原因及改進
喬振朋,趙澤方,姬彥洵,李爽,杜宇軒,王卓
(國網(wǎng)河南省電力公司直流中心,河南 鄭州 450007)
摘 要:對新投運的 1 000 kV 特高壓并聯(lián)電抗器產生乙炔原因展開分析,并通過返廠解體檢查確認乙炔產生原因為磁分路接地片與接地線連接不可靠,造成磁分路接地不可靠,發(fā)生接觸性放電。提出了磁分路夾件側屏蔽管新的接地方式,由原有的屏蔽管與夾件接觸接地更改為屏蔽管與夾件可靠絕緣后用接地線連接,避免因振動引起的接觸不可靠,為特高壓并聯(lián)電抗器生產、運維檢修提供了參考。
關鍵詞: 特高壓;并聯(lián)電抗器;磁分路;接地
中圖分類號:TM472 文獻標識碼:B 文章編號:1007-3175(2023)05-0029-07
Cause and Improvement of Acetylene Generation in the 1 000 kV UHV
Shunt Reactor Newly Put into Operation
QIAO Zhen-peng, ZHAO Ze-fang, JI Yan-xun, LI Shuang, DU Yu-xuan, WANG Zhuo
(State Grid Henan DC Center, Zhengzhou 450007, China)
Abstract: The paper first analyzes why the 1 000 kV UHV shunt reactor newly put into operation generates acetylene through disassembly inspection in the factory, and the cause of it is that the unreliable connection between the grounding strip and the grounding wire of the magnetic shunt leads to unreliable magnetic shunt grounding which makes contact discharge happen. Therefore, a new grounding mode of shielding pipes on the side of magnetic shunt clamps is proposed. It changes the grounding mode from the contact grounding between shielding pipes and clamps to using grounding wires to connect shielding pipes and clamps that have been insulated. This method can avoid unreliable contact caused by vibration,provide great reference for the production, operation and maintenance of UHV shunt reactors.
Key words: ultra high voltage; shunt reactor; magnetic shunt; grounding
參考文獻
[1] 官瀾,李光范,李博,等. 我國特高壓電力變壓器研制技術及發(fā)展[J] . 變壓器,2014,51(8):28-33.
[2] 譚風雷,陳昊,何嘉弘. 基于最佳分段和改進半物理模型的特高壓并聯(lián)電抗器頂層油溫預測[J] . 電網(wǎng)技術,2021,45(8):3314-3323.
[3] 劉旸,韓洪剛,隋新,等. 一起油浸式電抗器火災事故分析與防火對策研究[J] . 變壓器,2020,57(9):85-87.
[4] 束暢,章茜,高燃,等. 一起 1 000 kV 特高壓并聯(lián)電抗器內部故障分析[J] . 東北電力技術,2018,39(6):19-22.
[5] 趙若妤,馬宏忠,魏旭,等. 基于 EWT 及多尺度形態(tài)譜的高壓并聯(lián)電抗器故障診斷研究[J] . 電力系統(tǒng)保護與控制,2020,48(17):68-75.
[6] 解文鵬,鄭智聰. 特高壓并聯(lián)電抗器振動疲勞分析與研究[J] . 電子設計工程,2020,28(16):163-167.
[7] BHARTI Satyadharma, DUBEY Satya P.Controlled Shunt Reactor for UHVAC System Reactive Power Control[J].Recent Advances in Electrical & Electronic Engineering,2020,13(3):417-425.
[8] 吳書煜,馬宏忠,姜寧,等. 基于多物理場耦合的特高壓并聯(lián)電抗器振動噪聲仿真分析與實驗研究[J] .電力自動化設備,2020,40(3):122-127.
[9] 周兵,王延召,胡靜竹,等. 基于振動測量的并聯(lián)電抗器聲場計算[J] . 高壓電器,2019,55(11):105-112.