10 kV柱上一體化電容器多組投切方案應(yīng)用
呂樂,吳秋亮,沈威宇
(江蘇南瑞帕威爾電氣有限公司,江蘇 南京 211100)
摘 要:10 kV 線路配電網(wǎng)中大量的感性負(fù)荷需要從電網(wǎng)吸取大量的無功功率,導(dǎo)致線路的功率因數(shù)較低,末端電壓質(zhì)量較差。通過對柱上一體化電容器開發(fā)設(shè)計,并針對 10 kV 線路負(fù)荷和電壓無功需求波動數(shù)據(jù)分析,制定了 10 kV 線路無功補(bǔ)償多分組自動投切的解決方案,實際應(yīng)用成效表明,該方案解決了 10 kV 線路末端電壓低、功率因數(shù)較差、補(bǔ)償設(shè)備故障率高的問題。
關(guān)鍵詞: 配電網(wǎng); 柱上一體化電容器; 多分組補(bǔ)償; 電壓治理
中圖分類號:TM53 文獻(xiàn)標(biāo)識碼:B 文章編號:1007-3175(2024)03-0051-04
Application of Multi-Group Switching Scheme of 10 kV
On-Column Integrated Capacitor
LYU Le, WU Qiu-liang, SHEN Wei-yu
(Jiangsu NARI Power Electric Co., Ltd, Nanjing 211100, China)
Abstract: A large amount of inductive loads in the 10 kV line distribution network require a large amount of reactive power to be absorbed from the power grid, resulting in low power factor and poor terminal voltage quality of the line. Through the development and design of the on-column integrated capacitor, and the analysis of the fluctuation data of the load and voltage reactive demand of the 10 kV line, a multi-group automatic switching solution for the reactive power compensation of the 10 kV line was formulated. The practical application results show that the scheme solves the problems of low voltage at the end of the 10 kV line, poor power factor and high failure rate of compensation equipment.
Key words: distribution network; on-column integration capacitor; multi-group compensation; voltage governance
參考文獻(xiàn)
[1] 夏文雄,劉勇,趙鴻. 配電網(wǎng)電壓控制方案的探討[J].廣東電力,2002,15(4) :16-18.
[2] 郅建杰. 戶外柱上高壓無功動態(tài)補(bǔ)償裝置[J]. 電力設(shè)備,2006,7(9) :44-47.
[3] 胡頤,倪園琦. 無功補(bǔ)償技術(shù)在 10 kV 配電線路運行中的應(yīng)用研究[J]. 數(shù)字通信世界,2016(7) :79.
[4] 王雷. 無功補(bǔ)償計算及電壓無功投切判據(jù)分析[J]. 電力自動化設(shè)備,2001,21(6) :17-19.
[5] 田曉軼.10 kV 配電網(wǎng)中低壓無功補(bǔ)償裝置設(shè)計與應(yīng)用[J].科技尚品,2016(11) :139.
[6] 單永梅,包文俊,卿旺平,等.10 kV 農(nóng)村配電網(wǎng)桿上無功補(bǔ)償?shù)挠嬎鉡J]. 電力電容器與無功補(bǔ)償,2011,32(1) :16-19.