Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

500 kV電抗器局部放電故障處理分析

來源:電工電氣發(fā)布時間:2017-05-24 11:24 瀏覽次數(shù):7
500 kV電抗器局部放電故障處理分析
 
石海鵬,奇達(dá)博爾,姜楠,張倩然
(國網(wǎng)內(nèi)蒙古東部電力有限公司電力科學(xué)研究院,內(nèi)蒙古 呼和浩特 010020)
 
    摘 要:針對某500 kV 變電站帶電檢測時發(fā)現(xiàn)的500 kV 1 號電抗器A 相存在明顯的局部放電信號情況,根據(jù)油色譜檢測數(shù)據(jù),通過現(xiàn)場檢查、測試及故障分析,顯示該電抗器乙炔含量超標(biāo),初步判斷缺陷為電抗器爬梯對側(cè)的屏蔽件、定位件、緊固件等金屬部件發(fā)生懸浮放電,進(jìn)一步確認(rèn)是因為此處的鐵軛穿心桿螺母松動導(dǎo)致局部放電。根據(jù)故障原因,采取了相應(yīng)的故障檢修處理措施,有效消除了事故隱患。
    關(guān)鍵詞:電抗器;帶電檢測;局部放電;油色譜分析
    中圖分類號:TM471+.2     文獻(xiàn)標(biāo)識碼:B     文章編號:1007-3175(2017)04-0034-03
 
Disposal and Analysis of 500 kV Reactor Partial Discharge Fault
 
SHI Hai-peng, QI Da-boer, JIANG Nan, ZHANG Qian-ran
(State Grid East Inner Mongolia Electric Power Research Institute, Hohhot 010020, China)
 
    Abstract: In allusion to the condition that there obviously exists partial discharge signals in 500 kV No.1 Reactor A phase when the live detection carries out in certain 500 kV substation, according to the oil chromatographic detection data, via field inspection, test and fault analysis, it was found that the acetylene content of the reactor exceeded the standard, so as to initially judge that the drawback was the suspension discharge of metal parts such as shielding parts, locating piece, fasteners and other parts of the opposite side of the reactor ladder and to further affirm that the iron yoke rod nut loose led to partial discharge. In consideration of the failure causes, the corresponding corrective maintenance treatment measure was adopted to effectively eliminate accident potential.
    Key words: reactor; live detection; partial discharge; oil chromatographic analysis
 
參考文獻(xiàn)
[1] 楊玥,康琪. 內(nèi)蒙古電網(wǎng)電流互感器缺陷分析[J].內(nèi)蒙古電力技術(shù),2016,23(2):16-18.
[2] 劉金,王貴山,孫上元,等. 一起500 kV并聯(lián)電抗器故障分析[J]. 廣西電力,2015,38(3):33-35.
[3] GB/T 50150—2006 電氣裝置安裝工程電氣設(shè)備交接試驗標(biāo)準(zhǔn)[S].
[4] DL/T 596—2005 電力設(shè)備預(yù)防性試驗規(guī)程[S].